SS2KPB | Ex eb, Ex db, Ex nR, Ex ta | Explosive Atmosphere Cable Gland For all types of Lead Sheathed Unarmoured Cables

Double Seal, Internationally Approved, Explosive Atmosphere Cable Gland

• Effectively earths / grounds lead sheathed cables
• Direct & remote installation
• Superior levels of cable retention
• Displacement type flameproof seals
• Designed to prevent Coldflow
• Secure against self-loosening
• -60°C to +130°C
• Internationally marked, IECEx & ATEX

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications* Impact = Level 8, Retention = Class B
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
ATEX Certificate CML 18ATEX1322X, CML 18ATEX4314X
UKEX Certificate "CML 21UKEX1256X,CML 21UKEX4257X"
Code of Protection II 2G, II 1D, Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da
II 3G Ex nR IIC Gc, IM2 Ex db I Mb, Ex eb I Mb
Compliance Standards EN 60079-0,1,7,15,31
IECEx Certificate IECEx CML 18.0178X
Code of Protection Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex db I Mb, Ex eb I Mb
Compliance Standards IEC 60079-0,1,7,15,31
EAC Certificate C-GB.A07.B.04596/22
UkrSEPRO CU 19.0371X
CCC Certificate 2020322313002869
CCOE / PESO (India) Certificate Ex d: P548696, Ex e: P533772 Ex nR: P548695
INMETRO Approval TÜV 12.0879X
RETIE Approval 03866
Marine Approvals LRS: 01/00172, DNV: TAE00000Y, ABS: 20-LD1948801-PDA, BV: 43180/A1BV
SANS MS-XPL21804 21.0007X
Ingress Protection Rating ** IP66, IP67 & IP68
Cable Gland Material Brass, Electroless Nickel Plated Brass, Stainless Steel, Aluminium
Seal Material CMP SOLO LSF Halogen Free Thermoset Elastomer
Cable Type Unarmoured & Lead Sheathed, Lead Covered
Sealing Technique CMP Unique Displacement Seal Concept
Sealing Area(s) Cable Inner Lead Sheath or Lead Covering and Cable Outer Sheath
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation Tools Spanners
ECAS Certificate 24-03-106290/E24-03-110155/NB0007

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** When CMP installation accessories are used. Refer to Maintaining a Seal for further information.
*** IP68 tested to a minimum depth of 30 metres for 12 hours, alternate depths / durations can be provided upon request

Jump to technical illustration   

Certificates

Click here to view Certificates

Product Selection Table

Cable Gland SizeAvailable Entry Threads 'C' (Alternate Metric Thread Lengths Available)Diameter over Lead Sheath
'A'
Overall
Cable
Diameter
'B'
Across
Flats
'D'
Across
Corners
'D'
Protrusion
Length 'F'
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Ozs)
StandardOption
MetricThread Length (Metric) 'E'NPTThread Length
(NPT) 'E'
NPTMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20S16M200.59½'0.78¾"0.130.310.130.340.941.041.9520S16SS2KPB1RAPVC044.94
20SM200.59½'0.78¾"0.240.430.240.460.941.041.9520SSS2KPB1RAPVC044.59
20M200.59½'0.78¾"0.260.530.260.551.061.172.1520SS2KPB1RAPVC055.64
25M250.59¾'0.801"0.440.760.440.791.421.562.6225SS2KPB1RAPVC0910.58
32M320.591'0.981 ¼"0.671.000.671.041.611.782.6632SS2KPB1RAPVC1012.70
40M400.591 ¼'1.011 ½"0.931.230.931.261.972.172.7840SS2KPB1RAPVC1317.99
50SM500.591 ½'1.032"1.221.461.221.502.172.382.5850SSS2KPB1RAPVC1520.11
50M500.592'1.062 ½"1.401.681.401.732.362.602.7850SS2KPB1RAPVC1821.16
63SM630.592'1.062 ½"1.631.911.631.962.783.062.7863SSS2KPB1RAPVC2131.75
63M630.592 ½'1.573"1.862.131.862.202.953.252.8163SS2KPB1RAPVC2330.34
75SM750.592 ½'1.573"2.132.372.132.443.153.462.7875SSS2KPB1RAPVC2536.33
75M750.593'1.633 ½"2.412.572.412.673.313.642.9775SS2KPB1RAPVC2635.27
90M900.943 ½'1.694"2.623.042.623.134.254.684.4790SS2KPB1RAPVC31106.17
100M1000.943 ½'1.694"2.993.472.993.584.845.284.19100SS2KPB1RALSF33120.28
115M1150.944"1.735"3.393.703.393.855.255.785.06115SS2KPB1RALSF34188.72
130M1300.945"1.84-3.824.333.824.526.006.605.10130SS2KPB1RALSF35225.40
Dimensions displayed in inches unless otherwise stated
Cable Gland SizeAvailable Entry Threads 'C' (Alternate Metric Thread Lengths Available)Diameter over Lead Sheath
'A'
Overall
Cable
Diameter
'B'
Across
Flats
'D'
Across
Corners
'D'
Protrusion
Length 'F'
Combined Ordering Reference
(*Brass Metric)
ShroudCable
Gland
Weight
(Kgs)
StandardOption
MetricThread Length (Metric) 'E'NPTThread Length
(NPT) 'E'
NPTMinMaxMinMaxMaxMaxSizeTypeOrdering
Suffix
20S16M2015.0½'19.9¾"3.27.83.28.624.026.449.520S16SS2KPB1RAPVC040.14
20SM2015.0½'19.9¾"6.111.06.111.724.026.449.520SSS2KPB1RAPVC040.13
20M2015.0½'19.9¾"6.513.46.514.027.029.754.520SS2KPB1RAPVC050.16
25M2515.0¾'20.21"11.119.311.120.036.039.666.525SS2KPB1RAPVC090.30
32M3215.01'25.01 ¼"17.025.517.026.341.045.167.532SS2KPB1RAPVC100.36
40M4015.01 ¼'25.61 ½"23.531.223.532.150.055.070.540SS2KPB1RAPVC130.51
50SM5015.01 ½'26.12"31.037.231.038.255.060.565.550SSS2KPB1RAPVC150.57
50M5015.02'26.92 ½"35.642.635.644.060.066.070.550SS2KPB1RAPVC180.60
63SM6315.02'26.92 ½"41.548.541.549.970.577.670.563SSS2KPB1RAPVC210.90
63M6315.02 ½'39.93"47.254.247.255.975.082.571.563SS2KPB1RAPVC230.86
75SM7515.02 ½'39.93"54.060.254.061.980.088.070.575SSS2KPB1RAPVC251.03
75M7515.03'41.53 ½"61.165.261.167.984.092.475.575SS2KPB1RAPVC261.00
90M9024.03 ½'42.84"66.677.166.679.4108.0118.8113.590SS2KPB1RAPVC313.01
100M10024.03 ½'42.84"76.088.176.090.9123.0134.2106.5100SS2KPB1RALSF333.41
115M11524.04"44.05"86.094.186.097.9133.4146.7128.5115SS2KPB1RALSF345.35
130M13024.05"46.8-97.0110.197.0114.9152.4167.6129.5130SS2KPB1RALSF356.39
Dimensions displayed in millimeters unless otherwise stated

Technical Illustration

Additional Information

Lead Covered / Lead Sheathed Cables

In addition to the standard requirements for SWA cables, there is a set of special guidelines for lead covered cables intended for direct burial in the ground of hydrocarbons processing and refinery sites. These guidelines were introduced in the UK by the Oil Companies Material Association (OCMA) and responsibility for these were subsequently transferred to EEMUA, the Engineering Equipment and Material Users Association.

Read more

Visit our Knowledge Base for technical expertise and advice, gathered over CMP's 60+ years' experience in the art of terminating cable glands.

Sign up now